Watts to amps calculator

Amps = watts / volts, so 1,500 watts at 120 V is 12.5 amps, and 6.25 A at 240 V. Enter watts or amps, the voltage and the circuit type. The tool also shows the smallest standard breaker, with the National Electrical Code's 125% rule for loads that run 3 hours or more.

Amps12.5 Aat 120 V AC
Breaker, under 3 hours15 Asmallest standard size at or above the load
Breaker, 3 hours or more20 A15.6 A after the 125% rule
Kilowatts1.5 kW1,500 W

1,500 W at 120 V AC draws 12.5 A. Under 3 hours it fits a 15 A breaker; run 3 hours or more, it is a continuous load and needs 15.6 A of breaker, so 20 A. As a plug-in appliance it is also over the 12 A (80%) limit for one appliance on a 15 A circuit.

AC single-phase: amps = watts / (volts x power factor). Use 1 for heaters and incandescent lights; motor loads run lower, and their spec sheet gives the figure. Breaker sizes follow NEC 210.20(A) and the standard ratings in Table 240.6(A). An electrician sizes the circuit; the wire gauge must match the breaker.

Watts to amps chart (120 V and 240 V)

For heaters, lights and other loads with a power factor of 1. Motors draw a little more; see the formulas below.

Watts Amps at 120 V Amps at 240 V Amps at 12 V DC
100 W 0.83 0.42 8.33
200 W 1.67 0.83 16.7
300 W 2.5 1.25 25
400 W 3.33 1.67 33.3
500 W 4.17 2.08 41.7
600 W 5 2.5 50
700 W 5.83 2.92 58.3
750 W 6.25 3.13 62.5
800 W 6.67 3.33 66.7
900 W 7.5 3.75 75
1,000 W 8.33 4.17 83.3
1,200 W 10 5 100
1,500 W 12.5 6.25 125
1,800 W 15 7.5 150
2,000 W 16.7 8.33 166.7
2,400 W 20 10 200
2,500 W 20.8 10.4 208.3
3,000 W 25 12.5 250
3,500 W 29.2 14.6 291.7
4,000 W 33.3 16.7 333.3
4,500 W 37.5 18.8 375
5,000 W 41.7 20.8 416.7

How many amps is 1,500 watts?

1,500 W is 12.5 A at 120 V, 6.25 A at 240 V and 125 A from a 12 V battery through an inverter (before the inverter's own losses). It is the top of the range for plug-in space heaters (750 to 1,500 W) and the kettle in DOE's own worked example. At 12.5 A it sits above the 12 A that one plug-in appliance may use on a 15 A circuit, and run for 3 hours or more it needs 15.6 A of breaker, so a 20 A circuit with nothing else on it.

Amps to watts

Watts = amps x volts (x power factor on AC motor loads).

Amps Watts at 120 V Watts at 240 V Watts at 12 V DC
1 A 120 240 12
2 A 240 480 24
5 A 600 1,200 60
8 A 960 1,920 96
10 A 1,200 2,400 120
12 A 1,440 2,880 144
15 A 1,800 3,600 180
16 A 1,920 3,840 192
20 A 2,400 4,800 240
24 A 2,880 5,760 288
25 A 3,000 6,000 300
30 A 3,600 7,200 360
40 A 4,800 9,600 480
50 A 6,000 12,000 600

How many watts can a 15 or 20 amp circuit handle?

A 15 A circuit at 120 V carries 1,800 W at most, and 1,440 W (12 A) for a load that runs 3 hours or more. A 20 A circuit carries 2,400 W, or 1,920 W (16 A) for a continuous load. Everything plugged into the same circuit adds up, including the lamps and chargers you forget about.

Breaker 120 V, full 120 V, 80% 240 V, full 240 V, 80%
15 A 1,800 W 1,440 W 3,600 W 2,880 W
20 A 2,400 W 1,920 W 4,800 W 3,840 W
30 A 3,600 W 2,880 W 7,200 W 5,760 W
40 A 4,800 W 3,840 W 9,600 W 7,680 W
50 A 6,000 W 4,800 W 12,000 W 9,600 W

80% is the same limit as the NEC's 125% rule turned around: a breaker rated at least 125% of the load means the load stays at or under 80% of the breaker.

Common appliance amps

Running watts from manufacturer generator wattage guides (the top of the range where a guide gives one), divided by the voltage the appliance runs on. Compressors and pumps draw more for a moment as they start; the generator size calculator lists starting watts. The nameplate on your appliance gives its own figure.

Appliance Running watts Volts Amps
Refrigerator 400 120 3.33
Microwave (1,000 W) 1,500 120 12.5
Coffee maker 1,200 120 10
Space heater 1,500 120 12.5
Window AC (5,000 BTU) 600 120 5
Window AC (10,000 BTU) 1,500 120 12.5
Sump pump (1/2 hp) 1,050 120 8.75
Washing machine 1,000 120 8.33
TV (flat screen) 190 120 1.58
Garage door opener 720 120 6
RV air conditioner (13,500 BTU) 1,800 120 15
Electric clothes dryer 5,400 240 22.5
Electric water heater 4,500 240 18.8
Electric range burner (8 in) 2,100 240 8.75
Central AC (3 ton) 3,500 240 14.6

How to convert watts to amps

  1. DC (batteries, solar, 12 V systems): amps = watts / volts. 100 W at 12 V is 8.33 A.
  2. AC single-phase (house circuits): amps = watts / (volts x power factor). Use a power factor of 1 for heaters, kettles and incandescent lights. A motor load with a power factor of 0.8 draws more: 1,000 W at 120 V is 10.4 A instead of 8.33 A.
  3. AC three-phase: amps = watts / (1.732 x line-to-line volts x power factor). 10,000 W at 208 V with a power factor of 0.9 is 30.8 A per line.
  4. Amps to watts runs the same formulas the other way: watts = amps x volts (x power factor, x 1.732 for three-phase).

What size breaker do I need?

The National Electrical Code calls a load continuous when it runs at its full current for 3 hours or more. For those, the breaker has to be rated at least 125% of the load (NEC 210.20(A)), so a 12.5 A heater that runs all evening needs 15.6 A, which rounds up to the next standard size, 20 A. Separately, one plug-in appliance on a 15 or 20 A circuit may use no more than 80% of the circuit's rating (NEC 210.23(B)(1)). An electrician sizes new circuits; the wire gauge has to match the breaker, so never swap in a bigger breaker on its own.

Sources

Continuous-load rule, 80% plug-in limit and standard breaker sizes: NFPA 70, National Electrical Code, 2026 edition: Article 100 (continuous load, 3 hours or more), 210.20(A) (125 percent of the continuous load), 210.23(B)(1) (80 percent for one cord-and-plug appliance on a 15 or 20 A circuit; 210.23(A)(1) before the 2023 edition) and Table 240.6(A). Appliance watts: Honda generator wattage estimation guide, Champion Power Equipment generator wattage chart and Generac generator wattage worksheet. Watts = amps x volts: DOE Energy Saver (archived copy).

Related calculators