Water heater size calculator

A family of 4 needs a water heater with a first-hour rating of about 83 gallons: a50 gal gas tank rated that high, or an80 gal heat pump water heater. Two showers running at once need about 5.0 gpm from a tankless heater, or 184,100 BTU/h of gas when the water comes in at 50°F.

Sets the counts below: everyone showers in the same hour

First-hour rating83 galat least this, from the EnergyGuide label
Gas tank50 gallook for 83+; 50 gal run 77 to 93
Electric tankOver 50 gala larger tank or a heat pump
Heat pump tank80 gallook for 83+; 80 gal run 86 to 91

Your busiest hour uses about 83 gallons of hot water, so look for a water heater with a first-hour rating of at least 83 gallons: for example a 50 gal gas tank or an 80 gal heat pump water heater.

Gallons per use from DOE: shower 20, shave 2, hand dishwashing or food prep 3, dishwasher 7, top-load washer 25, front-load washer 15. The household preset assumes everyone showers in the same hour.

What size water heater do I need for my family?

The first-hour rating to look for, and the smallest tank of each type where a typical model reaches it. It assumes everyone showers in the same hour, plus one round of hand dishwashing or cooking. If your household staggers showers, use the calculator with your own counts.

Household First-hour rating Gas tank Electric tank Heat pump tank
1 person 23 gal 30 gal 40 gal 50 gal
2 people 43 gal 30 gal 40 gal 50 gal
3 people 63 gal 40 gal 50 gal 50 gal
4 people 83 gal 50 gal Over 50 gal 80 gal
5 people 103 gal Over 50 gal Over 50 gal Over 80 gal
6 people 123 gal Over 50 gal Over 50 gal Over 80 gal

Tank size alone does not decide it: 50 gal gas tanks run from 77 to 93 gallons of first-hour rating, depending on the burner. Read the rating on the EnergyGuide label or the spec sheet. Past the sizes listed, look at a larger tank, two tanks or a tankless heater.

What is a first-hour rating?

It is the number of gallons of hot water a tank heater can deliver in one hour, starting full, and it depends on the tank size and how fast the burner or elements reheat. DOE's method is to estimate your peak-hour demand, the hot water used in the busiest hour of the day, and pick a heater whose first-hour rating is at least that. It is printed on the EnergyGuide label as "Capacity (first hour rating)".

Use Hot water per use
Shower 20 gal
Shave 2 gal
Hand dishwashing or food prep 3 gal
Dishwasher load 7 gal
Top-load washer load 25 gal
Front-load washer load 15 gal

These are DOE's figures. AHRI's older worksheet uses more for appliances (14 gal for a dishwasher, 32 for a clothes washer); modern machines use less hot water, so we follow DOE.

Typical first-hour ratings by tank size:

Type Tank size First-hour rating
Gas 30 gal 49 to 67 gal
Gas 40 gal 59 to 72 gal
Gas 50 gal 77 to 93 gal
Electric 40 gal 54 to 55 gal
Electric 50 gal 62 to 69 gal
Heat pump 50 gal 59 to 67 gal
Heat pump 65 gal 75 to 80 gal
Heat pump 80 gal 86 to 91 gal

Gas and electric: A. O. Smith residential specification sheets (gas burners of 30,000 to 47,000 BTU/h, electric elements of 5,500 W). Heat pump: the middle half of models on the ENERGY STAR certified list, by tank size (50 gal covers 40 to 50 gal tanks, 65 gal covers 59 to 68, 80 gal covers 69 to 85).

What size tankless water heater do I need?

Add up the flow of everything you run at the same time, then work out the heat to warm it from the incoming water to 120°F. Gas input in BTU per hour for a condensing unit, by the city's winter water temperature:

Running at once Flow Minneapolis (40°F)New York (50°F)Atlanta (58°F)Houston (65°F)
1 shower 2.5 gpm 105,20092,10081,50072,300
1 shower + kitchen faucet 4.7 gpm 197,800173,100153,300136,000
2 showers 5.0 gpm 210,400184,100163,100144,700
2 showers + kitchen faucet 7.2 gpm 303,000265,200234,900208,300
3 showers 7.5 gpm 315,700276,200244,600217,000

Most whole-house gas units top out at 199,000 BTU/h, the most common input on the ENERGY STAR list; federal rules define a home gas tankless as under 200,000. Anything above that takes two units linked together. Electric units need far more power for the same job, in kW:

Running at once Minneapolis (40°F)New York (50°F)Atlanta (58°F)Houston (65°F)
1 shower 29.3 kW (122 A) 25.6 kW (107 A) 22.7 kW (95 A) 20.1 kW (84 A)
1 shower + kitchen faucet 55.1 kW (229 A) 48.2 kW (201 A) 42.7 kW (178 A) 37.9 kW (158 A)
2 showers 58.6 kW (244 A) 51.3 kW (214 A) 45.4 kW (189 A) 40.3 kW (168 A)
2 showers + kitchen faucet 84.4 kW (352 A) 73.8 kW (308 A) 65.4 kW (272 A) 58.0 kW (242 A)
3 showers 87.9 kW (366 A) 76.9 kW (320 A) 68.1 kW (284 A) 60.4 kW (252 A)

Amps at 240 V. Showers at 2.5 gpm, kitchen faucet 2.2 gpm. A big electric tankless needs its own heavy circuits, and an electrician has to confirm the panel and service can carry it.

Turned around, this is the flow a 199,000 BTU/h condensing gas unit can deliver at 120°F:

Winter water in Temperature rise Flow it can heat
Minneapolis, MN, 40°F 80°F 4.7 gpm
New York, NY, 50°F 70°F 5.4 gpm
Atlanta, GA, 58°F 62°F 6.1 gpm
Houston, TX, 65°F 55°F 6.9 gpm

That matches DOE's rule of thumb: at a 70°F rise, gas tankless heaters deliver about 5 gpm and electric ones about 2 gpm. With Minneapolis's 40°F winter water, one unit heats about 4.7 gpm: enough for two 2.0 gpm WaterSense showers, not quite two 2.5 gpm ones.

How cold is the water coming into my house?

Size a tankless heater for winter, when the water main is coldest. These are winter lows from the water-mains model in DOE's EnergyPlus software, fed with ASHRAE climate data for each city. DOE's own advice, if you do not know, is to assume 50°F, or to hold a thermometer under a cold tap.

City Winter water in Rise to 120°F
Miami, FL 77°F 43°F
Phoenix, AZ 67°F 53°F
Houston, TX 65°F 55°F
Los Angeles, CA 65°F 55°F
Dallas, TX 60°F 60°F
Atlanta, GA 58°F 62°F
Nashville, TN 54°F 66°F
Washington, DC 53°F 67°F
Seattle, WA 52°F 68°F
New York, NY 50°F 70°F
Boston, MA 47°F 73°F
Denver, CO 46°F 74°F
Chicago, IL 44°F 76°F
Minneapolis, MN 40°F 80°F
Fargo, ND 36°F 84°F

Water drawn from a reservoir or a shallow main can run colder than the model says. If your tap water feels colder than this in winter, measure it and use the custom field.

How many gallons per minute does a shower use?

Flow rates the calculator uses for each fixture:

Fixture Flow Basis
Shower 2.5 gpm Federal maximum; WaterSense heads use 2.0 or less
Kitchen faucet 2.2 gpm Federal maximum
Bathroom faucet 1.5 gpm WaterSense maximum (federal is 2.2)
Tub filling 4.0 gpm Our pick in the ASHRAE range of 1 to 6
Dishwasher 1.5 gpm Our pick in the ASHRAE range of 1 to 3
Clothes washer 2.0 gpm Our pick in the ASHRAE range of 1 to 6

A shower mixes in cold water, so it draws less than its full flow from the heater. Counting the full flow, as DOE's method does, leaves a margin. To measure a fixture, hold a bucket under it for a minute.

How the calculator works

Tank:

  1. Count what happens in your busiest hour: showers, shaves, dishes, dishwasher and washer loads.
  2. Multiply each by DOE's gallons per use and add them up. That is your peak-hour demand.
  3. Look for a heater with a first-hour rating at least that large. The tank sizes shown are the smallest where a typical model (the middle of the range below) reaches it.

Tankless:

  1. Flow = the gpm of every fixture running at once.
  2. Temperature rise = hot water setting minus incoming water temperature.
  3. Heat = flow x 8.33 lb per gallon x 60 minutes x rise, or 499.8 BTU per hour for each gpm and °F.
  4. Gas input = heat / efficiency (0.95 condensing, 0.81 non-condensing). Electric kW = heat / 3,412; amps = watts / 240.

Efficiencies: 0.95 is the median UEF of ENERGY STAR certified gas tankless models; 0.81 is the federal minimum UEF for gas tankless heaters. Gas and electric hookups are work for a licensed plumber, gas fitter or electrician.

Sources

Peak-hour method, gallons per use, 50°F incoming water, 120°F setting and gpm rules of thumb: DOE Energy Saver, Sizing a New Water Heater. Older appliance figures: AHRI water heater worksheet (2011). Gas and electric first-hour ratings: A. O. Smith residential gas and residential electric specifications. Heat pump ratings: ENERGY STAR certified heat pump water heaters. Gas tankless inputs and UEF: ENERGY STAR certified gas water heaters. Showerhead and faucet limits and the gas tankless UEF minimum: 10 CFR 430.32; the 200,000 BTU/h definition: 10 CFR 430.2. WaterSense: EPA, showerheads and bathroom faucets. Fill-rate ranges from the ASHRAE handbook, as listed in PNNL's instantaneous water heater sizing tool. Water-mains model: EnergyPlus Engineering Reference, Water Mains Temperatures, with monthly temperatures from ASHRAE 2021 climatic design conditions. BTU per kWh: EIA.